Product Name: Non-explosion-proof image type fire detector

Previews: 343

Release Date: 2019/09/09

I want to inquire the sales hotline: 18118109119

The image type fire detector is based on the image signal and the flame image sample, and analyzes the flame image software algorithm to collect the flame and monitor it. Widely used in buildings, factories, coal mines, thermal power plants and other environments, in line with GB15631-2008 industry standard requirements.

Six notes
1. Installation, inspection and maintenance must be performed by professionals, and this manual must be read carefully before operation.
2. Do not install, inspect and maintain the power supply, and do not loosen the lock nut at the back cover and the cable inlet when the power is on.
3. The detection part should be grounded as a whole.
4. Before wiring, check the external wiring for open circuit, short circuit or ground fault.
5. When the detection part is installed, care should be taken to protect the detection part window and keep the detection part window clean and undamaged.
6. Choose an appropriate installation angle and installation height to avoid detection blind spots caused by obstruction.

Seven debugging instructions
1. The image type fire detector can identify the flame through the sensor. When there is a flame, the flame image can be clearly seen through the display screen.
2. The detection part is powered by DC 24V; the image fire control cabinet is powered by 220V.
3. The detection part can detect visible flames, and the internal algorithm can automatically filter out false alarms caused by thermal interference and sunlight.
4. Connect two three-phase sockets to 220V power supply, and power on the whole machine. Power on time about 1min
5. After the product is turned on, the product is in the preheating state within 1min. After the preheating is completed, the detection part runs normally without alarm, the green operation indicator of the detection part is always on, the touch screen is lit and the video image is displayed.
6. After detecting the flame, the detection part will keep alarming. After the flame disappears, the detection part will stop alarming. You can also manually reset the detection part to stop alarming. Manually resetting the detection part will have a 1 minute warm-up time.
7. When the detection part fails, the flame alarm indicator (yellow) on the front panel of the detection part is always on until it is reset manually. The power-on time after resetting is about 1min.
8. The detection part has a power failure alarm function, that is, when the power is turned on, the fault relay is turned on, and once the power is turned off, the fault relay is turned off.

Eight installation instructions
Installation method of non-explosion-proof image flame detector;
图像 火焰 测器一般安装在保护区较高地方,检测范围覆盖所有目标和需要保护的地区并方便定期维护。 Non-explosion-proof image flame detectors are generally installed in higher areas of the protection area, and the detection range covers all targets and areas needing protection and facilitates regular maintenance.
图像 火焰 测器 安装使用一般向下倾斜10°,能同时检测下方和前方,还可以降低镜面受到的干预可能。 The installation and use of non-explosion-proof image flame detectors are generally inclined downward by 10 °, which can detect both the lower and the front, and reduce the possibility of interference on the mirror surface.
In the effective detection range of explosion-proof flame detectors, obstacles should be avoided, including transparent materials such as glass and other spacers. At the same time, the fire source should be directly directed to the detector to avoid indirect incident and reflection.

Installation height diagram

Installation method diagram

Nine wiring diagrams

Ten software instructions
After the device is powered on, the touch screen program starts automatically and enters the main interface. The main interface contains four areas, which are video area, information area, icon area, and key area, which are described below:

Video area
探测部分实时视频,画面上叠加显示探测器名称。 The real-time video of the detection part is displayed, and the detector name is superimposed on the screen.
Information area
Display the currently occurring alarm information. The data items include the time of occurrence, the name of the device, the number of fire points and the location (unit: meter). If the number of simultaneous alarms is greater than 5, the information area is divided into two identical parts for display.
Icon area:
The icons of the detection part 1-8 are displayed. At present, the number of camera icons on the system is 8. It supports expansion.
The detection part icons will have different display states.

Keypad

Filter by:

Camera: Includes "All Cameras", "Detector 1", "Detector 2", "Detector 3", "Detector 4", "Detector 5", "Detector 6", "Detector 7", and "Detector 8", the default is "All cameras";

  • Mode: Includes "Brief" and "Detail", default is "Brief"
  1. Brief mode : only record the start and end of a certain alarm in a certain detection section;
  2. Detailed mode : If the fire point or position changes during an alarm in a certain detection section, a record is generated.

Contains data items

  • Occurrence time: record the generation time;
  • Device name: the name of the detection part;
  • Changes : In brief mode, it includes two states (fire alarm start and fire alarm end); in detailed mode, it includes three states (or start, fire alarm end and update), during an alarm in a certain detection section, if If the number of fire points or location changes, a record will be generated, and its status is "Update";
  • Fire points: record the corresponding fire points;
  • Location (unit: meter): Location information of the main fire point.

Click the "Search" button to search; click the "OK" button to exit the interface.
2 System log

  1. Filter condition

Log categories: Includes "full log", "operation log", and "error log"

  • Complete LOG: complete log of the system, including program startup, user operations, and system failures;
  • Operation log: user's operation log;
  • Error LOG: System failure log (the current failure log is inaccurate and should include the detection of some connection disconnection logs and DVR connection disconnection logs).
  1. data

The log is mainly used by maintenance personnel when analyzing the cause of system failure. The following is only an example for the user to understand.

  • Operation LOG: 2017-03-13 10:18:11 2017-0 [OPR], [ssa_tlcd], -pressed CONSOLE_BUTTON_NEXT


Filter condition

  1. Camera: Includes "All Cameras", "Detector 1", "Detector 2", "Detector 3", "Detector 4", "Detector 5", "Detector 6", "Detector 7", and "Detector 8", the default is "All cameras";
  2. data item
  • Occurrence time: record the generation time;
  • Device name: the name of the detection part;
  • Changes: including "broken" and "linked";
  • IP address: The IP address corresponding to the detection part.
  1. Click the "Search" button to search; click the "OK" button to exit the interface.

Alarm linkage

Scenario example: 6 fire alarms have been triggered successively, the trigger sequence is detection section 8- detection section 5- detection section 6- detection section 4-detection section 2- detection section 3




If an alarm is over, the layout of the quad screen will change.
Front scene: 6 fire alarms have been triggered successively, the trigger sequence is detection part 8- detection part 5- detection part 6- detection part 4- detection part 2- detection part 3

Environmental conditions and power requirements
lWorking environment: -10 ℃ ~ 55 ℃
l Working humidity: 93% ± 3
l Power supply: 24VDC (18VDC ~ 30VDC) (detection part)
l Power supply: 220VAC (image fire control cabinet)
Three product life cycle: 8 years
Four key parts models
Lens Model: 1 / 3-12
Camera model: FL-800NS
Five structure and interface description
l Structure size
lJTGB-GY-TX-SSA3FD housing dimensions
Detection part: length 457mm, width 180mm, height 155mm
Monitoring part: length 598mm * width 598mm * height 1194mm