20L / 30L Automatic Fire Water Cannon Design

Release date: 2017.07.25 Views: 1731 times

Design basis

1. "Code for Design of Automatic Fire Alarm System" GB 501162013

2. "Code for Fire Protection of Building Design" GB 500162006

3. 《Technical Regulations for Automatic Fire Cannon Fire Extinguishing System》 CECS245: 2008

4. "Code for Design of Automatic Sprinkler System" GB GB500842001 (2005 Edition)

5. "Automatic Tracking and Positioning Jet Fire Extinguishing System" GB 252042010

6. "Code for Design of Fixed Fire Cannon Fire Extinguishing System" GB 503382003

7. "Code for Construction and Acceptance of Automatic Fire Alarm System" GB 501662007


自动消防水炮灭火装置 系统工作原理: Working principle of automatic fire water monitor system:

自动消防水炮灭火装置 可以全天候探测保护范围内的一切火情。 ZDMS0.8 / 20S-ZQ automatic fire water cannon fire extinguishing device can detect all fire conditions within the protection range 24/7. In the event of a fire, the fire extinguishing device will immediately detect and quickly locate the source of the fire, and then intelligently open the solenoid valve and output a signal to the on-site control box to start the water pump and spray water by the water nozzle. After one cycle of water spraying (the cycle time can be reasonably adjusted according to the site's needs), the system will intelligently stop the water spraying and the nozzle will automatically reset. If there is a new fire source, the system will intelligently repeat the above actions until the fire is completely cleared. The on-site control device can also switch the manual / automatic function of the fire extinguishing device, so as to meet the needs of on-site emergency manual operation.

1. Installation of fire extinguishing device

① The fire extinguishing device is hoisted and installed, so that the gun can fully rotate 360 ° horizontally and -90 ° ~ 30 ° vertically, and can shoot directly below the fire extinguishing device, so that there is no blind spot in the protected area.

② The fire extinguishing device should be firmly fixed on the truss of the building to ensure that during spraying, it will not be shaken due to the back-force reaction and affect the accuracy of the fire extinguishing.

③ The integrated on-site control box is installed 1.5m from the ground, and a "manual controller" is installed in the box. Can be used to easily operate fire extinguishing equipment.

④ The installation position of the on-site control panel should be able to observe the corresponding fire monitor and approach the exit direction. Set the installation position according to the interior design and the actual situation on site.


Third, the system wiring

1)水炮到现场区域控制箱:RVV14x1.5(水炮电源线控制线)+RVV2x1.5(摄像头电源线) ( 1) Water monitor to the field area control box: RVV14x1.5 (water monitor power cable control line) + RVV2x1.5 (camera power cable)

2)红紫外火焰探测器 到现场区域控制箱: RVV4x1.5(探测器电源线信号线) ( 2) Red UV flame detector to the field area control box: RVV4x1.5 (detector power line signal line)

阀到现场区域控制箱: RVV2x1.5(电动阀电源线) (3) Electric valve to field control box: RVV2x1.5 (electric valve power cable)

4 )现场区域控制箱到末端试水装置: RVV3x1.5(末端试水装置电源线)+RVSP2x1.5(信号总线) ( 4 ) On-site area control box to end water test device: RVV3x1.5 (power cable for end water test device) + RVSP2x1.5 (signal bus)

5 )现场区域控制箱到消防报警主机: RVV3x2.5(电源线)+RVSP2x1.5(信号总线)+RVSP2x1.5(远程控制线) ( 5 ) On-site area control box to fire alarm host: RVV3x2.5 (power line) + RVSP2x1.5 (signal bus) + RVSP2x1.5 (remote control line)

6 )水炮到消防报警主机: SYV-75-5(视频线)。 ( 6 ) Water monitor to the fire alarm host: SYV-75-5 (video cable). (When the water cannon does not have video, no video or remote control cable is required, and the system does not have remote control function)

(7) Fire alarm host to pump room: RVV4x1.5 (start pump line, open pump feedback line).

:1、 由于水炮需 360度旋转,电缆线必须预留足够长度,否则会损坏设备! Note : 1. As the water cannon needs to rotate 360 degrees, the cable must be reserved with a sufficient length, otherwise the equipment will be damaged!


Fourth, the system power

Fire extinguishing device, electric valve, detector voltage is 24V, powered by the control box, and its central equipment is powered by 220V.


Five, system ground

This system uses dedicated grounding, and the grounding resistance should be no more than 5 ohms. When using joint grounding, the grounding resistance should be no more than 1 ohm.


Construction requirements

Pipeline installation should be carried out in accordance with the corresponding standards in electrical construction; fire protection pipelines should be laid separately and cannot be co-managed with other system lines; in the construction process, they should be closely coordinated with the professional of civil equipment and coordinated.


Seven, pump room requirements

1. The pump room must be able to provide sufficient water pressure, and to ensure that the inlet pressure of the fire extinguishing device at the most unfavorable point of the pipeline reaches 0.8 MPa.

2. The pump room must be equipped with voltage stabilization and pressure relief devices.

3. A pressure gauge is set at the water outlet of the fire pump, the maximum indicated pressure is 2.5 MPa, an automatic drain valve and a return pipe are set at the water pipe of the fire pump;

4. Provide one fire pump and one pressure controller. The pump flow rate should not only meet the water output of the fire extinguishing device, but also other fire protection equipment that is turned on at the same time.


术参数: Eight, ZDMS0.8 / 20S-ZQ automatic fire water cannon fire extinguishing device technical parameters:

Rated working pressure: 0.8MPa Jet flow: 20L / S

≤50m 定位时间 ≤55S Protection radius: ≤50m positioning time ≤55S

Inlet flange: DN65 Installation height: 6m-22m

Horizontal rotation: 0 ° --- + 360 ° (adjustable setting)

Vertical pitch: -90 ° ---- 30 ° (adjustable setting)

Rear gravity: ≈1000N gun body weight: about 16Kg


Nine, the matters not mentioned in this description refer to the current national standards, and standardize implementation.

I. Relevant design specifications adopted in this project

1. "Code for Design of Automatic Fire Alarm System" GB 501162013

2. "Code for Fire Protection of Building Design" GB 500162006

3. 《Technical Regulations for Automatic Fire Cannon Fire Extinguishing System》 CECS245: 2008

4. "Code for Design of Automatic Sprinkler System" GB GB500842001 (2005 Edition)

5. "Automatic Tracking and Positioning Jet Fire Extinguishing System" GB 252042010

6. "Code for Design of Fixed Fire Cannon Fire Extinguishing System" GB 503382003

7. "Code for Construction and Acceptance of Automatic Fire Alarm System" GB 501662007


Design of waterway for large space intelligent no fire extinguishing system

Design range

Take the project intelligent fire extinguishing system, using ZDMS0.8 / 20S-ZQ type automatic tracking and positioning jet fire extinguishing device as a case.


Technical parameters of ZDMS0.8 / 20S-ZQ-01 automatic tracking and positioning jet fire extinguishing device:

Rated working pressure: 0.8MPa Jet flow: 20L / S

≤50m 定位时间 ≤55S Protection radius: ≤50m positioning time ≤55S

Inlet flange: DN65 Installation height: 6m-22m

Horizontal rotation: 0 ° --- + 360 ° (adjustable setting)

Vertical pitch: -90 ° ---- 30 ° (adjustable setting)

Rear gravity: ≈1000N gun body weight: about 16Kg


3. For personnel-intensive places, fire cannons are equipped with columnar mist-like stepless conversion devices.


Fourth, the fire pool and fire pump room

1.Provide one use and one backup fire pump, and can ensure that the pressure at the most unfavorable point of the pipeline fire extinguishing device inlet reaches 0.8MPa.

2. Provide 1 use and 1 spare booster pump;

3. This system calculates the water injection of a maximum of two automatic jet fire extinguishing devices at the same time.

Volume = 20L / S × 60 × 60 × 2 = 144m³;

4, the pipe network should be able to prevent frost, and should be provided with a drain valve.


Five, elevation and size

1. For this project drawing, the elevation is in meters, and the others are in millimeters;

2. Pipeline elevation refers to the center elevation of the pipe;

3. If there is any error in the size of the figure, the plan shall prevail.


Control method

1. Automatic fire monitor is a set of sprinkler system with automatic tracking and positioning. The system has automatic control and central control.

There are three control methods for remote control in the production room and emergency control on site.


Seven, pipeline and equipment installation

1. The pipeline adopts thick hot-dip galvanized steel pipe;

2, connection: pipe diameter less than 100mm using threaded connection, greater than or equal to 100mm using clamp groove

connection;

3. After the system construction and installation are completed, the entire system operation test should be performed before acceptance.


Eight, pipeline pressure test

1. Pipeline test pressure is 1.2Mpa;

2. The test point of the hydrostatic strength test shall be set at the lowest point of the system pipe network. When filling the pipe network with water, the

The air should be drained and the pressure should be increased slowly. After reaching the test pressure, the voltage should be stabilized for 30 minutes.

No deformation, and the pressure drop should not be greater than 0.05MPa.


Nine, pipeline corrosion and insulation

1. Where the galvanized layer of the pipeline is damaged, two anti-rust paints are applied;

2. Anti-galvanized steel pipe rust paint for buried pipes;

3. Outdoor exposed fire-fighting pipes are insulated according to the national standard 87S159 Figure 2.


X. The parts not described in this description shall be constructed in accordance with relevant national regulations or atlases.


Eleven, ZDMS0.8 / 20S automatic fire water cannon fire extinguishing equipment pipeline installation

Automatic fire water cannon fire extinguishing device is installed with signal valve, electric valve, fire extinguishing device in order, and finally fixed bracket. Of course, if you are sure, you can install the fixed bracket first. It is worth noting that because of different installation environments, the fixing bracket has different installation styles. Please choose the most suitable installation style according to your site conditions. Except for the inexhaustible installation of the water supply pipeline, it shall be carried out strictly in accordance with the pipeline installation specifications.

Ranch